Thermal Ageing of Dry Cellulose Paper Impregnated with Different Insulating Liquids—Comparative Studies of Materials Properties
Open Access
Abstract
Natural and synthetic esters are increasingly being chosen instead of mineral oil for environmental and fire safety reasons. However, their use in power transformers is limited due to insufficiently well-understood ageing processes affecting their properties and the properties of cellulosic materials impregnated with them. The research results presented in many scientific papers prove that the use of esters slows the ageing process of cellulosic materials. This article presents the results of research aimed at answering the question of whether the effect of slowing the ageing process will also occur in the case of insulation with very low initial moisture. The answer to this question will allow us to better understand the role of water in the ageing process of the transformer’s insulation system. The thermal ageing process was carried out at a temperature of 150 °C in closed systems. The degree of cellulose polymerisation was taken as a measure of the degree of paper ageing. Great attention was paid to measuring the water content in both paper and electro-insulating liquids at various stages of their ageing. Furthermore, measurements of the properties of electro-insulating liquids were made, which are considered markers of ageing. The test results obtained indicate that in the case of a dry insulation system, corresponding to the initial moisture of the new units, the type of liquid used to impregnate the cellulosic material does not significantly affect its depolymerisation process. However, in the case of paper impregnated with natural esters, a lower dynamic of moisture increase in insulation was observed.Keywords
Funding Information
- Politechnika Poznańska (0711/SBAD/4616)
This publication has 27 references indexed in Scilit:
- Thermal Aging Study of Alternative Liquids for Oil-Paper High-Voltage Insulation in Current Transformers2022
- On Some Imperative IEEE Standards for Usage of Natural Ester Liquids in TransformersIEEE Access, 2020
- Thermal aging analysis of mineral oil and natural ester immersed windings2020
- Risk of Fire and Explosion in Electrical Substations Due to the Formation of Flammable MixturesScientific Reports, 2020
- In-service ageing comparison study of natural ester and mineral oil filled distribution transformers2019
- Cellulose insulation in oil-filled power transformers: Part I - history and developmentIEEE Electrical Insulation Magazine, 2006
- Cellulose insulation in oil-filled power transformers: part II maintaining insulation integrity and lifeIEEE Electrical Insulation Magazine, 2006
- Interaction mechanisms of natural ester dielectric fluid and kraft paper2005
- Degradation of cellulosic insulationin power transformers.Part 3: Effects of oxygen and water on ageing in oilIEE Proceedings - Science, Measurement and Technology, 2000
- Acidic activation of cellulose and its esterification by long-chain fatty acidJournal of Applied Polymer Science, 1999