Method for identifying ageing in epoxy‐mica composite insulation used in rotational machines through modelling of dielectric relaxation
Authors:
Open Access
- 25 February 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in High Voltage
- Vol. 5 (2) , 184-190
Abstract
Dielectric response analysis, performed in time domain and frequency domain is one of the interesting methods used for condition assessment of high voltage equipment. In this article, the degradation of epoxy‐mica composite insulation which is widely used in rotating machines has been investigated through frequency domain spectroscopy measurements. Artificial ageing of the carefully prepared stator bar insulation sample was performed through simultaneous application of high temperature and electric field in a designated environmental chamber for specific durations. To study the effect of temperature, the measurements were performed at temperatures ranging from 20 to 60°C at different ageing status. Following experimental work, the measurement results were modelled using Havriliak–Negami model and ageing sensitive parameters were extracted. To study the effect of temperature, the measurements were performed at temperatures ranging from 20 to 60°C. The modelled results matched well with the experimental measurements and certain model parameters sensitive to the ageing condition were identified. The numerical relationships between the insulation status of the stator bar and the aforementioned parameters were identified. It was observed that the nature of the numerical relationship remains identical in the investigated temperature range, although the coefficients vary to some extent.Keywords
This publication has 23 references indexed in Scilit:
- Causes of cyclic mechanical aging and its detection in stator winding insulation systemsIEEE Electrical Insulation Magazine, 2019
- Identification of slot discharges in rotating machine insulation system using variable frequency PD measurementHigh Voltage, 2018
- Study on FDS characteristics of oil‐immersed paper insulation bushing under non‐uniform moisture contentIET Science, Measurement & Technology, 2018
- Effect of measurement temperature on power transformer insulation diagnosis using frequency‐domain spectroscopyIET Science, Measurement & Technology, 2017
- Condition monitoring and diagnosis of power equipment: review and prospectiveHigh Voltage, 2017
- Electrical-Based Diagnostic Techniques for Assessing Insulation Condition in Aged TransformersEnergies, 2016
- Dielectric and physico-chemical properties of epoxy-mica insulation during thermoelectric agingIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Statistical Health Reasoning of Water-Cooled Power Generator Stator Bars Against Moisture AbsorptionIEEE Transactions on Energy Conversion, 2015
- Measurement variations of insulation resistance/polarization index during utilizing time in HV electrical machines – A surveyMeasurement, 2015
- Condition monitoring and diagnostics of motor and stator windings – A reviewIEEE Transactions on Dielectrics and Electrical Insulation, 2013