Study on AC Flashover Performance and Discharge Process of Polluted and Iced IEC Standard Suspension Insulator String
- 26 December 2006
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 22 (1) , 472-480
Abstract
Based on the results of experimental investigations performed on the polluted and iced IEC standard suspension insulator strings of 3~21 units, the ac flashover performance and discharge process are discussed in this paper. It is put forward that the icing stress product (ISP), defined as the product of the ice-layer conductivity and the ice layer weight per centimeter of dry arc distance can be taken as a characteristic parameter to indicate the effect of ice accretions and contaminants on the flashover voltage. The flashover stress of an ice-covered insulator string can be expressed as a power function of ISP and has a linear relationship with the length of the insulator string. The partial arc of an iced insulator string is initiated by the breakdown of the air gaps between the tips of icicles and iced insulator surface and the persistence is much longer than that of a polluted insulator stringKeywords
This publication has 12 references indexed in Scilit:
- Selection of Station Insulators With Respect to Ice and Snow—Part I: Technical Context and Environmental ExposureIEEE Transactions on Power Delivery, 2005
- Study of flashover performance and voltage correction of DC insulator in icing districts of altitude of 2500 m and below2003
- Flashover performance of IEEE standard insulators under ice conditionsIEEE Transactions on Power Delivery, 1997
- The cold-fog test [for outdoor insulators]IEEE Transactions on Power Delivery, 1996
- AC flashover performance of insulators covered with artificial iceIEEE Transactions on Power Delivery, 1995
- Long range transported pollutants and conductivity of atmospheric ice on insulatorsIEEE Transactions on Power Delivery, 1993
- Withstand voltage characteristics of insulator string covered with snow or iceIEEE Transactions on Power Delivery, 1991
- Minimum Flashover Voltage of Iced InsulatorsIEEE Transactions on Electrical Insulation, 1983
- Flashover test of Artificially iced InsualtorsIEEE Transactions on Power Apparatus and Systems, 1982
- AC Flashover Tests at Project UHV on Ice-Coated InsulatorsIEEE Transactions on Power Apparatus and Systems, 1970