The impacts of uncoordinated charging of electrical vehicles (EVs) under high penetration on distribution transformers is studied. It is shown that it may cause prolonged overload condition leading to accelerated assets loss of life and increased hazard of failure. To mitigate the impact, a fuzzy logic-based algorithm is devised. It provides a performance index for distribution grid operator using four main inputs: 1) EV battery state of charge; 2) required state of charge for the next trip; 3) estimated time of EV departure; and 4) customer comfort level. A decision-support tool is proposed by which the distribution grid operators can utilize the output of the fuzzy systems to receive a suggestion whether to delay the charging of each EV and pay the incentive to the EV owner. The data for the city of College Station, Texas, USA including temperature, price of electricity and load profile are collected from various sources to simulate different use cases. The example illustrates how the proposed EV management approach could mitigate the impact of EV charging on the transformer loss of life and hazard of failure. The main advantage of the proposed approach is the low cost and ease of design implementation. The information that needs to be sent from the consumer to the distribution system operator is minimized, which helps in maintaining costumers' privacy.