The power of paper - Effects of power quality distortions on electrical drives and trasformer life in paper industries
Authors:
- Mehdi RadmehrMRMehdi Radmehr
- Shahrokh FarhangiSFShahrokh Farhangi
- Adel NasiriANAdel Nasiri
- 27 August 2007
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Industry Applications Magazine
- Vol. 13 (5) , 38-48
Abstract
The results of a one-year power-quality study (2004-2005) in the Mazandaran Wood and Paper Industries (MWPI) are presented in this article. The effects of voltage distortion on the operation of electric drives are discussed. To provide detailed analysis of the system, one of the DC motor drive systems is simulated using Matlab/Simulink in the presence of voltage sag and the results are presented. Additionally, the effects of harmonics on the loss of distribution transformers are described. Using the actual data, the LOL of distribution transformers is calculated. The results of power-quality monitoring at MPWI are also presented. These investigations reveal that active or passive power filtering is required for at least five supply transformers in the mill.Keywords
This publication has 5 references indexed in Scilit:
- A low cost approach to improve the performance of an adjustable speed drive (ASD) under voltage sags and short-term power interruptions2002
- Commercial application experiences with SMESPower Engineering Journal, 1999
- Evaluating harmonic-induced transformer heatingIEEE Transactions on Power Delivery, 1996
- Practical distribution transformer models for harmonic studiesIEEE Transactions on Power Delivery, 1995
- Estimation methods for power system harmonic effects on power distribution transformersIEEE Transactions on Industry Applications, 1994