Numerical simulation of scale‐model smoke contamination of upper atrium levels by a channelled balcony spill plume
- 20 July 2012
- journal article
- research article
- Published by Wiley in Fire and Materials
- Vol. 37 (8) , 581-596
Abstract
Smoke contamination of balconies due to a channelled spill plume at a lower level in an atrium might occur during a fire and could affect occupant safety during an evacuation. Previous experimental work has investigated the extent of smoke contamination, and this work describes a numerical modelling comparison of the experiments using the Fire Dynamics Simulator (FDS) computational fluid dynamics programme. Temperature, severity and height of smoke contamination are selected as the key parameters for comparison. The predictions of severity and height of smoke contamination are generally similar to the experimental results using a ‘most severe point assessment of smoke contamination’ assessment method. Although predicted temperatures are slightly lower than experimental values, FDS temperature slice files can be used at the most severe smoke contaminated point using a 10 °C temperature rise. This 10 °C threshold matches the criterion proposed in the previous experimental research. On the basis of the comparisons for the height of smoke contamination, the simulation results generally match a previously proposed equation for the height of smoke contamination above a balcony spill plume. Copyright © 2012 John Wiley & Sons, Ltd.Keywords
This publication has 14 references indexed in Scilit:
- Experimental investigation on influence of different transverse fire locations on maximum smoke temperature under the tunnel ceilingInternational Journal of Heat and Mass Transfer, 2012
- Physical Scale Modeling of Smoke Contamination in Upper Balconies by a Channeled Balcony Spill Plume in an AtriumJournal of Fire Sciences, 2009
- Application of FDS to Adhered Spill Plumes in AtriaFire Technology, 2009
- Entrainment by adhered two-dimensional plumesFire Safety Journal, 2008
- The Balcony Spill Plume: Entrainment of Air into a Flow from a Compartment Opening to a Higher Projecting BalconyFire Technology, 2007
- Using FDS to Simulate Smoke Layer Interface Height in a Simple AtriumFire Technology, 2007
- Numerical simulation of axi-symmetric fire plumes: accuracy and limitationsFire Safety Journal, 2003
- Simulation on Natural Smoke Filling in Atrium with a Balcony Spill PlumeJournal of Fire Sciences, 2001
- Numerical simulations on balcony spill plumeFire and Materials, 1999
- Measurements of balcony smoke flowFire Safety Journal, 1995