Experience with an on-line monitoring system for 400 kV XLPE cables
Authors:
- K. PolsterKPK. Polster
- B.A. FruthBFB.A. Fruth
- D.W. GrossDGD.W. Gross
- 24 December 2002
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 515-520
Abstract
The use of high voltage cables is today recommended and sometimes mandatory in order to avoid environmental concerns of the public, especially when the power system crosses areas of dense population. The reunion of the former GDR with the Federal Republic of Germany has stimulated the interest in this settlement especially for the city of Berlin, where the increase of energy demand requires the use of innovative solutions. The paper reports the activities that BEWAG, the electrical utility of Berlin, performs in order to investigate the feasibility of setting up an urban bulk power connection using 400 kV XLPE cables. During a first accelerated voltage endurance test (at CESI in Milan/Italy) on cables and accessories of six major European manufacturers several failures in joints and SF/sub 6/ terminations were encountered. Therefore the cable links for the actual second testing period were additionally equipped with partial discharge sensors for an insulation monitoring system. Sensors of this type will in the future be integrated into the cable accessories to improve after laying quality control. It is thought that this partial discharge test will replace high voltage DC-tests which were found unsuitable for the 400 kV XLPE cable technology.Keywords
This publication has 7 references indexed in Scilit:
- Partial discharge mechanisms in solid insulation systems2003
- Combination of frequency spectrum analysis and partial discharge pattern recording2002
- Phase resolving partial discharge pattern acquisition and frequency spectrum analysis2002
- Modelling of streamer discharges between insulating and conducting surfaces2002
- The importance of statistical characteristics of partial discharge dataIEEE Transactions on Electrical Insulation, 1992
- Partial discharge. X. PD in gas-insulated substations-measurement and practical considerationsIEEE Electrical Insulation Magazine, 1992