Full‐scale shaking table test of a base‐isolated medical facility subjected to vertical motions
Authors:
- 20 May 2013
- journal article
- research article
- Published by Wiley in Earthquake Engineering & Structural Dynamics
- Vol. 42 (13) , 1931-1949
Abstract
SUMMARY: Base isolation is a well known technology that has been proven to reduce structural response to horizontal ground accelerations. However, vertical response still remains a topic of concern for base‐isolated buildings, perhaps more so than in fixed‐base buildings as isolation is often used when high performance is required. To investigate the effects of vertical response on building contents and nonstructural components, a series of full‐scale shaking table tests were conducted at the E‐Defense facility in Japan. A four‐story base‐isolated reinforced concrete building was outfitted as a medical facility with a wide variety of contents, and the behavior of the contents was observed. The rubber base isolation system was found to significantly amplify vertical accelerations in some cases. However, the damage caused by the vertical ground motions was not detrimental when peak vertical floor accelerations remained below 2 g with three exceptions: (1) small items placed on shelves slid or toppled; (2) objects jumped when placed on nonrigid furniture, which tended to increase the response; and (3) equipment with vertical eccentricities rocked and jumped. In these tests, all equipment and nonstructural components remained functional after shaking. Copyright © 2013 John Wiley & Sons, Ltd.Keywords
This publication has 12 references indexed in Scilit:
- Seismic Resistance Capacity of High-Rise Buildings Subjected to Long-Period Ground Motions: E-Defense Shaking Table TestJournal of Structural Engineering, 2010
- The Influence of Isolator Hysteresis on Equipment Performance in Seismic Isolated BuildingsEarthquake Spectra, 2010
- A substructure shaking table test for reproduction of earthquake responses of high‐rise buildingsEarthquake Engineering & Structural Dynamics, 2009
- Experimental and analytical studies on the response of freestanding laboratory equipment to earthquake shakingEarthquake Engineering & Structural Dynamics, 2008
- BASE-ISOLATION DESIGN PRACTICE IN JAPAN: INTRODUCTION TO THE POST-KOBE APPROACHJournal of Earthquake Engineering, 2005
- Non‐linear response analyses of rectangular rigid bodies subjected to horizontal and vertical ground motionEarthquake Engineering & Structural Dynamics, 2002
- Construction of a three–dimensional, large–scale shaking table and development of core technologyPhilosophical Transactions of the Royal Society A: Mathematical, Physical and Engineering Sciences, 2001
- 1. Vertical Response of Twelve Structures Recorded during the Northridge EarthquakeEarthquake Spectra, 1998
- 1. Characteristics of Free‐Field Vertical Ground Motion during the Northridge EarthquakeEarthquake Spectra, 1995
- Motions of rigid bodies and criteria for overturning by earthquake excitationsEarthquake Engineering & Structural Dynamics, 1982