Application of a Rogowski Coil Sensor for Separating Internal and External Partial Discharge Pulses in Power Transformers
- 2 November 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 70 (8) , 8509-8516
Abstract
Partial discharge (PD) measurement is an essential tool for evaluating the health condition of a transformer insulation system. The Conventional PD measurement systems have a major drawback since they cannot discriminate the internal PD pulses and external pulse-shaped interferences, especially in online and on-site conditions. Various de-noising techniques (e.g. wavelets) have been also used in the literature, which is effective for extracting the PD signal from the noisy signals or classifying the PD types. However, the PD pulses and some of the randomly external pulse-shaped interferences have similar time-frequency characteristics, which makes them difficult to separate. In this paper, a new cost-effective and simple logic method is proposed for the separation of these interferences. This uses the polarity comparison of the output voltages of the Rogowski Coil (RC) sensor, mounted on the bushing, and measurement impedance, connected to the test tap. The same polarity represents the internal pulse, while the opposite polarity indicates the external pulses. A distribution transformer ( $20/0.4\ {\bm{kV}},\ 500\ {\bm{kVA}})$ and a condenser bushing ( $72.5\ {\bm{kV}})$ were considered to evaluate the performance of the proposed system. The results confirm the effectiveness of the proposed PD measurement system for separating the pulses.Keywords
This publication has 17 references indexed in Scilit:
- Improving the numerical indices proposed for the FRA interpretation by including the phase responseInternational Journal of Electrical Power & Energy Systems, 2016
- Design of PCB Rogowski Coil and Analysis of Anti-interference PropertyIEEE Transactions on Electromagnetic Compatibility, 2016
- High-Voltage Test and Measuring Techniques2014
- Investigation on Rogowski coil performance for structuring its design methodologyIET Science, Measurement & Technology, 2013
- A method for discriminating original pulses in online partial discharge measurementMeasurement, 2011
- IEEE Standard for High-Voltage Switchgear (Above 1000 V) Test Techniques--Partial Discharge Measurements2009
- Mutual inductances comparison in Rogowski coil with circular and rectangular cross-sections and its improvement2008
- High-Frequency Model of the Rogowski Coil With a Small Number of TurnsIEEE Transactions on Instrumentation and Measurement, 2007
- Improved Detection of Power Transformer Winding Movement by Extending the FRA High Frequency RangeIEEE Transactions on Power Delivery, 2005
- Practical implementation of ultrawideband partial discharge detectorsIEEE Transactions on Electrical Insulation, 1992