Analysis of power consumption of high frequency resistance spot welding systems

Authors:

Abstract
For analysis of power consumption of resistance spot welding systems field-circuit modelling is required. It includes both 2D eddy-current FEA analysis for estimation of the leakage impedance of transformer and P-Spice program for the circuit simulation. It is shown that the design of the transformer influences on the output current and power consumption. We used the equivalent circuit of three-winding transformer which differs from well-known equivalent circuit of such a transformer. This circuit is based on replacing the three-winding transformer with two two-winding transformers. The mutual impact of these transformers is modelled as a change of EMF on the terminals of their secondary windings by magnetic leakage fields. We investigated several transformer designs for the 7.5 kHz resistance spot welding system. Designs differ interleaving of primary and secondary windings and the number of primary winding coils. They have different leakage inductances and different coupling factors for the leakage flux. Calculations have shown that it is necessary to reduce the leakage inductances of transformers for increasing the operating current if output voltage is constant for all investigated transformers. On the bases of the investigations we developed transformer with the operating current 11 kA and frequency 7.5 kHz. It has almost twice less power consumption than the basic one. This result is confirmed experimentally.