Following Hurricane Maria, the restoration of Puerto Rico's transmission and distribution system revealed a significant difference in customer recovery. Last-mile customers, i.e., those located in distant areas were deprived of electricity for up to a year during the recovery process. The purpose of this work is to explore differences in power system recovery when maximizing customers served (MCS) as opposed to maximizing load served (MLS). This study leverages the optimizer Recovery Simulator and Analysis (RSA) to achieve this. System recovery evaluates Customer Hours of Lost Electricity Service (CHoLES) and compares. Results reveal that while the time to recover 100% of the customers is unchanged, the recovery time to restore 90% of the customers, which is the metric used to measure recovery time for major events, is improved. Study results suggest that the recovery objective selected can have significant impact on how quickly a majority of customers are recovered.