Equivalent Model of Photovoltaic Power Station Considering Different Generation Units’ Fault Current Contributions
Open Access
Abstract
The fault current calculation model of photovoltaic (PV) power stations is usually treated as a capacity weighted equivalent model of a single PV generation unit (PVGU). However, in the same PV power station, different PVGUs have various fault current characteristics. As a result, there are significant differences in fault current characteristics between a PVGU and a PV power station. It means that the existing capacity weighted equivalent model cannot be used for accurately describing the fault current contributions from a practical PV power station. In this paper, the fault behaviors of the PVGUs located at different access points of a PV power station are firstly analyzed. The difference in PVGUs’ fault current contributions is identified and reflected with the activation states of current limiters that are employed for PV inverters. The activation states are represented by a theoretical expression so as to distinguish the PVGUs’ fault contributions. Further, based on the proposed theoretical expression, a novel algorithm is developed for sorting all PVGUs included in a PV power station. The multi-machine calculation model is deduced in order to exactly express the fault current contribution from a PV station. Finally, some simulation tests are conducted. The tested results verify the effectiveness of the proposed calculation model. It can provide support for calculating the protection setting of power grid connected with large-scale PV stations.Keywords
Funding Information
- State Key Laboratory Of Alternate Electrical Power System With Renewable Energy Sources (LAPS19009)
- State Key Laboratory of Power Grid Safety and Energy Conservation (China Electric Power Re-search Institute) (JBB51202001892)
This publication has 25 references indexed in Scilit:
- Establishment of fault current characteristics for solar photovoltaic generator considering low voltage ride through and reactive current injection requirementRenewable and Sustainable Energy Reviews, 2018
- Adaptive protection coordination scheme against the staircase fault current waveforms in PV‐dominated distribution systemsIET Generation, Transmission & Distribution, 2018
- Modeling and fault analysis of solar photovoltaic grid-connected systems under solar radiation fluctuation considerationInternational Transactions on Electrical Energy Systems, 2018
- Fault Models of Inverter-Interfaced Distributed Generators Within a Low-Voltage MicrogridIEEE Transactions on Power Delivery, 2016
- Flexible Grid Connection Technique of Voltage-Source Inverter Under Unbalanced Grid Conditions Based on Direct Power ControlIEEE Transactions on Industry Applications, 2015
- Fault Analysis for Distribution Networks With Current-Controlled Three-Phase Inverter-Interfaced Distributed GeneratorsIEEE Transactions on Power Delivery, 2015
- IMICV fault analysis method with multiple PV grid-connected inverters for distribution systemsElectric Power Systems Research, 2015
- Overview of power inverter topologies and control structures for grid connected photovoltaic systemsRenewable and Sustainable Energy Reviews, 2014
- Fault response of inverter interfaced distributed generators in grid-connected applicationsElectric Power Systems Research, 2014
- Fault Analysis on Distribution Feeders With High Penetration of PV SystemsIEEE Transactions on Power Systems, 2012