DWT-Based Detection and Transient Power Direction-Based Location of High-Impedance Faults Due to Leaning Trees in Unearthed MV Networks
Authors:
- Nagy I. ElkalashyNENagy I. Elkalashy
- Hatem A. DarwishHDHatem A. Darwish
- Abdel-Maksoud I. TaalabATAbdel-Maksoud I. Taalab
- Mohamed A. IzzularabMIMohamed A. Izzularab
- 26 December 2007
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 23 (1) , 94-101
Abstract
Electrical faults due to leaning trees are common in Nordic countries. This fault type has been studied in and it was found that the initial transients in the electrical network due to the associated arc reignitions are behavioral traits. In this paper, these features are extracted using the discrete wavelet transform (DWT) to localize this fault event. Wireless sensors are considered for processing the DWTs on a residual voltage of different measuring nodes that are distributed in the network. Therefore, the fault detection is confirmed by numerous DWT processors over a wide area of the network. The detection security is also enhanced because the DWT responded to a periodicity of the initial transients. The term for locating the faulty section is based on the polarity of a specific frequency bandpower computed by multiplying the DWT detail coefficient of the residual current and voltage at each measuring node. The fault due to a leaning tree occurring at different locations in an unearthed 20-kV network is simulated by the alternate transients program/electromagnetic transients program and the arc model is implemented using the universal arc representation. Test cases provide evidence of the efficacy of the proposed technique.Keywords
This publication has 14 references indexed in Scilit:
- A novel selectivity technique for high impedance arcing fault detection in compensated MV networksEuropean Transactions on Electrical Power, 2007
- Design of a Concept and a Wireless ASIC Sensor for Locating Earth Faults in Unearthed Electrical Distribution NetworksIEEE Transactions on Power Delivery, 2006
- High Impedance Fault Detection Based on Wavelet Transform and Statistical Pattern RecognitionIEEE Transactions on Power Delivery, 2005
- Universal Arc Representation Using EMTPIEEE Transactions on Power Delivery, 2005
- A novel technique for high impedance fault identificationIEEE Transactions on Power Delivery, 1998
- Practical high-impedance fault detection on distribution feedersIEEE Transactions on Industry Applications, 1997
- Arcing fault detection for distribution feeders: security assessment in long term field trialsIEEE Transactions on Power Delivery, 1995
- Digital simulation of fault arcs in power systemsEuropean Transactions on Electrical Power, 1991
- Unique aspects of distribution system harmonics due to high impedance ground faultsIEEE Transactions on Power Delivery, 1990