Numerical simulation of an experimental atrium fires in combined natural and forced ventilation by CFD
- 2 January 2019
- journal article
- research article
- Published by Taylor & Francis in International Journal of Ventilation
- Vol. 19 (1) , 1-24
Abstract
This study investigates the measurements data attained in Murcia Atrium fire tests (Gutiérrez-Montes, Sanmiguel-Rojas, Viedma, & Rein) using general CFD code, CFX-16.2 ( CFX-16.2, ANSYS, Inc.). Experiments were executed by burning heptane as a fuel for three different fires capacities, (1.32, 2.28 and 2.34 MW). Historically, CFX was validated with experimental data for compartment fires including natural ventilation only. In this paper validation was performed for developing fires during transient period in a large space, including the effect of combined natural and forced ventilation. Two different combustion models i.e. Non-combustion model and Eddy Dissipation Model (EDM) were used to represent the combustion of heptane. Four different approaches were employed to determine the predicted dynamic behavior of the smoke height and to evaluate the accuracy of CFX predictions. The results display CFX predictions have a reasonable concord with the experimental data. Therefore, CFX can be a valid tool for performance-based engineering to evaluate the smoke systems required for complex enclosed structures.Keywords
This publication has 31 references indexed in Scilit:
- Froude Modelling of Fire Phenomena: Observation of Fire-induced Smoke Movement in Basement Structure for Firefighting PurposeProcedia Engineering, 2017
- Effects of vertical shaft arrangement on natural ventilation performance during tunnel firesInternational Journal of Heat and Mass Transfer, 2014
- Determination of the Smoke Layer Interface Height for Hot Smoke Tests in Big HallsJournal of Fire Sciences, 2009
- Toxicity of Fire SmokeCritical Reviews in Toxicology, 2002
- CFD Fire Simulations with Four Turbulence Models and Their CombinationsJournal of Fire Sciences, 1999
- Smartfire: an Intelligent Cfd Based Fire ModelJournal of Fire Protection Engineering, 1999
- Comparison of the fire model predictions with experiments conducted in a hangar with a 15 meter ceiling1996
- Numerical studies on the transient behaviour of a fire plume and ceiling jetMathematical and Computer Modelling, 1993
- Field Modelling of Fire in Forced Ventilated EnclosuresCombustion Science and Technology, 1987
- An Experimental Study of Upper Hot Layer Stratification in Full-Scale Multiroom Fire ScenariosJournal of Heat Transfer, 1982