Frequency-Coupling Impedance Model Based Analysis of a High-Frequency Resonance Incident in an Actual MMC-HVDC System
- 7 September 2020
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (6) , 2963-2971
Abstract
Recently, a high-frequency resonance (HFR) incident has been captured in an actual HVDC project of China Southern Power Grid, which is regarded as a new stability issue caused by the interaction between the modular multilevel converter (MMC) and the weak ac grid. To investigate this event, this paper proposes a stability analysis method based on the frequency-coupling impedance model (FCIM). First, the FCIMs of the MMC and the ac grid are established in abc-frame individually with the frequency coupling effect of the MMC taken into account. Next, they are aggregated into a two-by-two impedance matrix by numerical calculation. Then, based on the aggregated FCIM, a criterion is developed to locate the HFR modes and to evaluate their stability. Finally, the results obtained from FCIM-based analysis are verified by electromagnetic transient (EMT) simulations as well as the field measurements.Keywords
Funding Information
- National Natural Science Foundation of China (51737007, 51925701)
- China Southern Power Grid (ZBKJXM20170065)
This publication has 29 references indexed in Scilit:
- High-Frequency Harmonic Resonance Suppression in High-Speed Railway Through Single-Phase Traction Converter With LCL FilterIEEE Transactions on Transportation Electrification, 2016
- A Parallel Contour Integral Method for Eigenvalue Analysis of Power SystemsIEEE Transactions on Power Systems, 2016
- Three-Phase Harmonic and Sequence Components Measurement Method Based on mSDFT and Variable Sampling Period TechniqueIEEE Transactions on Instrumentation and Measurement, 2016
- Couplings in Phase Domain Impedance Modelling of Grid-Connected ConvertersIEEE Transactions on Power Electronics, 2016
- A Review of Passive Power Filters for Three-Phase Grid-Connected Voltage-Source ConvertersIEEE Journal of Emerging and Selected Topics in Power Electronics, 2015
- The Use of Averaged-Value Model of Modular Multilevel Converter in DC GridIEEE Transactions on Power Delivery, 2014
- Harmonic Resonance Assessment to Traction Power-Supply System Considering Train Model in China High-Speed RailwayIEEE Transactions on Power Delivery, 2013
- A New Procedure to Derive Transmission-Line Parameters: Applications and RestrictionsIEEE Transactions on Power Delivery, 2005
- Parallel Transmission Lines Fault Location Algorithm Based on Differential Component NetIEEE Transactions on Power Delivery, 2005
- Measurements of the Frequency-Dependent Impedance of a Thin Wire With Ground ReturnIEEE Transactions on Power Delivery, 2005