Effect of Step Response Measurement Arrangement on the Correction of Lightning Impulses Measured with Ultra-High-Voltage Dividers
Authors:
- 1 July 2018
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-2
Abstract
Ultra-high-voltage (UHV) lightning impulse voltage dividers normally have limited bandwidth, which deforms the waveform of the measured impulse. The step response of the dividers can be used to correct the measured waveforms by deconvolution, reducing the errors of the impulse parameters. The circuit arrangement for measuring step response, however, may influence the measured step response and the corrected impulse waveforms. In this paper, two circuit arrangements of step response measurement were used in investigating the effect of different step responses on the corrected impulses. The lightning impulses measured using two UHV dividers were corrected and the errors of the impulse parameters before and after correction were determined. The results show that accurate correction can be made for the dividers without being affected by the external connection arrangement of the step response measurement.Keywords
This publication has 1 reference indexed in Scilit:
- Interactions between two dividers used in simultaneous comparison measurements (of power system impulses)IEEE Transactions on Power Delivery, 1989