Insulation Degradation Mechanism Analysis Under Different Applied Voltages and Frequencies

Authors:

Abstract
Insulation material degradation rate is a function of applied electric field, temperature changes, service time, and other environmental factors. In most cases, this rate determines the lifespan of the associated electrical component. Multiple offline test techniques have been developed to detect the insulation material quality. One of the most popular techniques is the dissipation factor (tanδ), or power factor (cos(90°-δ)) test. In practice, the two terms are interchangeable when the phase angle, δ, is very small. How different frequencies of applied voltage affect the dissipation factor of the insulation materials is still an open issue. Along these lines, a mathematical model has been developed, based on fundamental electric field knowledge, to show mechanisms of degradation, and provide modes of interpreting dissipation factor results under various frequencies of applied fields. A “critical voltage” is proposed in this context for insulation degradation assessment. To demonstrate this degradation mechanism theory and the use of “critical voltage,” partial dielectric frequency response experiment was performed on a piece of degraded 35 kV XLPE cable.