Robust control of HVAC plant I: modelling
- 1 February 2000
- journal article
- research article
- Published by SAGE Publications in Building Services Engineering Research & Technology
- Vol. 21 (1) , 53-61
Abstract
A simulation model of a discharge air temperature plant is developed using SLMULINK within the MATLAB environment. Step response results from an open-loop form of this model are correlated with experimental data with good agreement. Settings for a fixed-parameter PID controller are 'benchmarked' from manufacturers' recommendations and optimised at local plant operating conditions using cost-function minimisation. A closed-loop form of the plant model is simulated using these controller specifications, revealing significant lack of robustness due to plant nonlinearity when the manufacturers' recommendations were applied. The locally optimised PID controller performed well, but this would require extensive understanding of plant characteristics to be achieved in practice. In a second part of this paper, a method is developed that achieves robust control for a wide variety of plant operating conditions based on simple a priori data about the plant.Keywords
This publication has 3 references indexed in Scilit:
- Flow characteristics in circuits using three-port modulating control valvesBuilding Services Engineering Research & Technology, 1995
- Neural network control of a non-linear heater batteryBuilding Services Engineering Research & Technology, 1994
- Advanced control for BEMS: A model-based predictive approachBuilding Services Engineering Research & Technology, 1992