Study on the influence of building aerodynamic shadows on the heat transfer performance of natural draft dry cooling towers
Open Access
- 1 November 2023
- journal article
- research article
- Published by AIP Publishing in AIP Advances
- Vol. 13 (11)
Abstract
Previous studies have shown that the heat transfer of air cooling towers is mainly affected by crosswind. To improve the cooling performance of air-cooled towers under crosswind and the efficiency of power plants, this paper studies the influence mechanism of buildings on the heat dissipation performance of natural draft dry cooling towers (NDDCTs). The numerical simulation of a 2 × 1000 MW NDDCT is carried out to analyze the distribution of the aerodynamic shadow area and its influence on the heat transfer performance of the NDDCT. The study found that at a wind speed of 12 m/s, the heat dissipation efficiency of the NDDCT under the influence of the original building decreased by 4.74%, and the total ventilation volume decreased by 2595.76 kg/s. When the NDDCT was located in the aerodynamic shadow wake area of the building, the heat dissipation efficiency increased by 8.36%. This shows that the aerodynamic shadow area of the building will lead to deflection deceleration and a steady flow effect of the flow field near the tower base, which has a double-sided effect on the heat transfer of the NDDCT. By adjusting the interference of the aerodynamic shadow wake area of the building on the NDDCT, the high wind speed sensitivity and the heat dissipation deviation of the two towers can be reduced.Keywords
Funding Information
- Hebei Province Outstanding Youth Fund (E2020502001)
This publication has 27 references indexed in Scilit:
- Dimensional characteristics of wind effects on the performance of indirect dry cooling system with vertically arranged heat exchanger bundlesInternational Journal of Heat and Mass Transfer, 2013
- Effects of ambient winds on the thermo-flow performances of indirect dry cooling system in a power plantInternational Journal of Thermal Sciences, 2013
- A proposed stack configuration for dry cooling tower to improve cooling efficiency under crosswindJournal of Wind Engineering and Industrial Aerodynamics, 2010
- An overview about the study of downwash effects on dispersion of airborne pollutantsEnvironmental Modelling & Software, 2004
- A wind tunnel study of dense gas dispersion in a stable boundary layer over a rough surfaceAtmospheric Environment, 2001
- Numerical simulation of fluid flow and thermal performance of a dry-cooling tower under cross wind conditionJournal of Wind Engineering and Industrial Aerodynamics, 1999
- The effect of the heat exchanger arrangement and wind-break walls on the performance of natural draft dry-cooling towers subjected to cross-windsJournal of Wind Engineering and Industrial Aerodynamics, 1995
- A study of the unfavorable effects of wind on the cooling efficiency of dry cooling towersJournal of Wind Engineering and Industrial Aerodynamics, 1995
- Wind Tunnel Experiments on Cooling Tower Plumes: Part 2—In a Nonuniform Crossflow of Boundary Layer TypeJournal of Heat Transfer, 1989
- Wind Tunnel Experiments on Cooling Tower Plumes: Part 1—In Uniform CrossflowJournal of Heat Transfer, 1989