Use of low frequency harmonic components as a signature to detect arcing on HTV silicone rubber in salt-fog
Authors:
- 25 June 2003
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 212-215
Abstract
This paper presents the results of using the low frequency harmonics of leakage current as a measure of dry band arcing in salt-fog. Sleeved high temperature vulcanized (HTV) silicone rubber rods were tested under 0.25, 0.40 and 0.60 kV/cm in salt-fog at two different salinities, i.e. 1000 and 2500 /spl mu/S/cm. The leakage current was measured and analyzed using fast Fourier transform (FFT). The results show that as the electric field increases, the fundamental component of the leakage current decreases and both the third and fifth harmonic components increase. Also, increasing the salinity of the fog increases both the third and fifth harmonic components with no significant change in the fundamental component. In general, harmonic components increased only when arcing occurred; thus providing a signature for the dry band arcing activities.Keywords
This publication has 7 references indexed in Scilit:
- Leakage current patterns on artificially polluted composite insulators2002
- Leakage current analysis and infrared spectroscopy of outdoor insulating materials aged in a salt-fog test2002
- Analysis of leakage current wave forms for field-aged and new composite insulators2002
- Leakage current patterns on contaminated polymeric surfacesIEEE Transactions on Dielectrics and Electrical Insulation, 1999
- Study on the frequency characteristics of leakage current waveforms of artificially polluted 12t suspension insulators by the clean fog method1999
- Leakage currents on non-ceramic insulators and materialsIEEE Transactions on Dielectrics and Electrical Insulation, 1999
- Ageing tests of polymeric housing materials for non-ceramic insulatorsIEEE Electrical Insulation Magazine, 1998