PMU-based line and transformer parameter estimation
Authors:
- 1 March 2009
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-8
Abstract
An algorithm is proposed to estimate the parameters of transmission lines and transformers using synchronized phasor measurements at both ends of the element. It uses a simultaneous state and parameter estimation algorithm applied to an artificial system to find the parameters of the line or transformer. A number of successive data sets can be used to improve the accuracy of the estimation. The method can be combined with a resampling scheme to obtain very accurate values of constant parameters. It is also shown that this algorithm can track the values of time-varying parameters, including sudden changes resulting from line compensation or tap changing. The performance of the algorithm was tested by estimating all the parameters of the IEEE 30 bus test system, including one parameter that changes with time.Keywords
This publication has 20 references indexed in Scilit:
- Monitoring amplitude, frequency and damping of power system oscillations with PMU measurements2008
- Transmission line’s parameter estimation using state estimation algorithms2008
- An Alternative for Including Phasor Measurements in State EstimatorsIEEE Transactions on Power Systems, 2006
- Identification of Network Parameter ErrorsIEEE Transactions on Power Systems, 2006
- Power system state estimation: modeling error effects and impact on system operation2005
- Measurement of transmission line parameters from SCADA data2005
- Observability analysis and measurement placement for systems with PMUs2005
- Combined State Estimation and Measurement CalibrationIEEE Transactions on Power Systems, 2005
- Synchronized phasor measurements-a historical overview2003
- Estimation of parameter errors from measurement residuals in state estimation (power systems)IEEE Transactions on Power Systems, 1992