Abstract
At present, the main control strategies for HVDC projects are derived from the ABB strategy and the SIEMENS strategy. In this paper, the difference between the two strategies in dealing with the inverter side ac fault is firstly analysed. It is pointed out that commutation failure (CF) with the SIEMENS strategy lasts longer than that with the ABB strategy, for the reason that the SIEMENS strategy still relies on PI regulation during the fault period and its response speed is relatively slow compared to the decreasing rate of the extinction angle. Then, a compound phase‐shifting control is proposed for the SIEMENS strategy, including control considering the rising rate and magnitude of dc current as well as control considering both unbalance and magnitude of ac voltage. The simulation results show that the application of the compound phase‐shifting control contributes to shortening the duration of CF, as well as improving power recovery and system response after fault cleared.