Improvement of HVDC commutation failure response based on compound phase‐shifting control
Open Access
- 1 January 2017
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in The Journal of Engineering
- Vol. 2017 (13) , 1473-1477
Abstract
At present, the main control strategies for HVDC projects are derived from the ABB strategy and the SIEMENS strategy. In this paper, the difference between the two strategies in dealing with the inverter side ac fault is firstly analysed. It is pointed out that commutation failure (CF) with the SIEMENS strategy lasts longer than that with the ABB strategy, for the reason that the SIEMENS strategy still relies on PI regulation during the fault period and its response speed is relatively slow compared to the decreasing rate of the extinction angle. Then, a compound phase‐shifting control is proposed for the SIEMENS strategy, including control considering the rising rate and magnitude of dc current as well as control considering both unbalance and magnitude of ac voltage. The simulation results show that the application of the compound phase‐shifting control contributes to shortening the duration of CF, as well as improving power recovery and system response after fault cleared.Keywords
This publication has 5 references indexed in Scilit:
- Direct-Current Predictive Control Strategy for Inhibiting Commutation Failure in HVDC ConverterIEEE Transactions on Power Systems, 2014
- Commutation Failure Analysis in Multi-Infeed HVDC SystemsIEEE Transactions on Power Delivery, 2010
- Commutation failure in single- and multi-infeed HVDC systems2006
- Detailed Modeling of CIGRÉ HVDC Benchmark System Using PSCAD/EMTDC and PSB/SIMULINKIEEE Transactions on Power Delivery, 2005
- A novel method to mitigate commutation failures in HVDC systems2002