Origin of dielectric processes in aged oil impregnated paper
- 29 June 2017
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 24 (3) , 1625-1635
Abstract
Oil impregnated paper in power transformers deteriorates in long-term operation, which leads to the variations of its dielectric characteristics. This paper focuses on investigating the generation mechanism of the dielectric processes in oil impregnated paper and their variations with thermal aging. Firstly, a set of thermally stimulated current tests with bias-voltages were conducted in distinguishing the dielectric processes and revealing their generation mechanism. Secondly, the standard thermally stimulated current spectrum and the M″ spectrum of 0–1000 h aged samples were joint analyzed in investigating the variations of dielectric processes in thermal aging process. Finally, additional experiments of moisture, acidity and microscopic observation were conducted in explaining these variations. It is concluded that three dielectric processes can be found in oil impregnated paper, i.e. the dipole polarization, the interfacial polarization and the electric conduction. These processes are all strengthened with thermal aging. The generation of molecules with strong polarity, the structural changes in insulating paper, and the generation of hydrogen ions are responsible for the strengthening of these processes sequentially. This investigation on distinguishing dielectric processes and obtaining their mechanism can promote further understanding on oil impregnated paper and provide information for insulation design in power transformers.Keywords
This publication has 42 references indexed in Scilit:
- Dielectric spectroscopy and gas chromatography methods applied on high-voltage transformer oilsIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Frequency Response of Oil Impregnated Pressboard and Paper Samples for Estimating Moisture in Transformer InsulationIEEE Transactions on Power Delivery, 2006
- The Influence of Levelling-off Degree of Polymerisation on the Kinetics of Cellulose DegradationCellulose, 2005
- A Moisture-in-Oil Model for Power Transformer Monitoring—Part II: Experimental VerificationIEEE Transactions on Power Delivery, 2005
- Electrical transport modelling in organic electroluminescent devicesJournal of Physics: Condensed Matter, 2002
- Practical life-assessment technique for aged transformer insulationIEE Proceedings A Science, Measurement and Technology, 1993
- Effect of bias on thermally stimulated current (TSC) in irradiated MOS devicesIEEE Transactions on Nuclear Science, 1991
- Development of oil-dissolved hydrogen gas detector for diagnosis of transformersIEEE Transactions on Power Delivery, 1990
- The Nature of Aromatic MoleculesScientific American, 1972
- Phosphorescence and electron traps II. The interpretation of long-period phosphorescenceProceedings of the Royal Society of London. A. Mathematical and Physical Sciences, 1945