A phasor filtering algorithm on eliminating the effect of fault transient components for the frequency domain fault location
Authors:
- 1 October 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 2, 1507-1512
Abstract
Among fault location schemes, the frequency domain method is more available than time domain. However, its application is restricted by reason of the effect of decaying dc and other transient components, which cannot be removed by DFT during fault transient. Most researches on the phasor filtering algorithm are based on the field of protection. Thereby, the accuracy and stability cannot meet demand for fault location. This paper proposed a novel filtering algorithm to extract the precise fundamental component by means of solving a linear equation, which was transformed from a non-linear equation concerning the error caused by decaying dc with DFT. Then, typical signal models were constructed to demonstrate that, the proposed algorithm is accurate, stable and with the anti-interference ability of noises e.g. non-integer harmonic frequency components. Finally, the proposed filtering algorithm was applied to the frequency domain fault location method. Simulation results show that the filtering algorithm can eliminate the effect of fault transient components and extraordinarily improve the precision of frequency domain fault location method.Keywords
This publication has 12 references indexed in Scilit:
- A new filtering technique to eliminate decaying DC and harmonics for power system phasor estimation2006
- A New Half-Cycle Phasor Estimation AlgorithmIEEE Transactions on Power Delivery, 2005
- Fault location algorithms for super high voltage power transmission lines2004
- A fault location technique for two and three terminal lines using high frequency fault clearing transients2003
- Complete elimination of DC offset in current signals for relaying applications2002
- Removal of DC offset in current and voltage signals using a novel Fourier filter algorithmIEEE Transactions on Power Delivery, 2000
- Removal of DC-offset in current waveforms using digital mimic filteringIEEE Transactions on Power Delivery, 1995
- A recursive least error squares algorithm for power system relaying and measurement applicationsIEEE Transactions on Power Delivery, 1991
- Transmission line fault location using digital fault recordersIEEE Transactions on Power Delivery, 1988
- A New Algorithm for Digital Impedance RelaysIEEE Transactions on Power Apparatus and Systems, 1979