Depolarization Current Measurements on Field-Aged XLPE Cable Insulation
Authors:
- 1 October 2008
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 00849162,p. 21-24
Abstract
Laboratory tests on field aged and unaged cables were performed using DC depolarization current measurements. Aged cables with water trees showed high dielectric losses and depolarization currents as compared with the reference, unaged cable. Both the area under the depolarization current waveform and dielectric loss factor, tandelta, increased with DC poling and the applied AC voltage, respectively. A new indicator of the insulation aging derived from the measured current is proposed to rate the degree of aging of cable insulation. This indicator increases with the poling field, and a DC poling voltage less than 50% of the nominal peak value of the cable operating voltage is sufficient to obtain reliable values. The cable insulation aging indicator could be a useful tool for monitoring the operating condition of cables in service and help utilities to develop cable replacement programs based on the actual state of the cable insulation conditions.Keywords
This publication has 8 references indexed in Scilit:
- Some considerations on the selection of optimum location, timing, and technique, for diagnostic tests2008
- On-site Diagnostic Tests on Polymer Insulated Cables Using Depolarization Current Measurements2007
- Correlation between dc polarization and failure characteristics of XLPE and EPR aged with ac voltage in a wet environmentIEEE Transactions on Dielectrics and Electrical Insulation, 2005
- Applications of dielectric spectroscopy in time and frequency domain for HV power equipmentIEEE Electrical Insulation Magazine, 2003
- Dielectric spectroscopy in time and frequency domain for HV power equipment. I. Theoretical considerationsIEEE Electrical Insulation Magazine, 2003
- Correlation between AC breakdown strength and low frequency dielectric loss of water tree aged XLPE cablesIEEE Transactions on Power Delivery, 1998
- The Current Comparator1988
- Diagnostic Method for Power Cable InsulationIEEE Transactions on Electrical Insulation, 1986