Synchronous Generator Eccentricities Modeling by Improved MWFA and Fault Signature Evaluation in No-Load E.M.F.s and Current Spectra
Authors:
- 1 June 2008
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 200-205
Abstract
In this paper an accurate modeling of air-gap length function in polar and interpolar regions of non- isotropic synchronous generators is presented, for use in the MWFA (modified winding function approach), to obtain accurate machine simulations with eccentricities. Air-gap in interpolar regions is usually poorly modeled in current literature. Inductances obtained by the improved MWFA have been compared with 3D-FEM model obtained ones. External no-load e.m.f. and current spectra have been evaluated for a medium-power alternator with non-aligned rotor, and with various static and dynamic eccentricity degrees. Fault signatures appear all over the spectra, with variable entities, whose comprehensive evaluation can be used for fault severity assessment.Keywords
This publication has 5 references indexed in Scilit:
- Extension of winding function theory for nonuniform air gap in electric machineryIEEE Transactions on Magnetics, 2002
- A novel method for modeling dynamic air-gap eccentricity in synchronous machines based on modified winding function theoryIEEE Transactions on Energy Conversion, 1998
- On-line current monitoring and application of a finite element method to predict the level of static airgap eccentricity in three-phase induction motorsIEEE Transactions on Energy Conversion, 1998
- Vertical hydraulic generators experience with dynamic air gap monitoringIEEE Transactions on Energy Conversion, 1992
- Dynamic Measurement And Analysis Of Air Gap Variations In Large Hydroelectric GeneratorsIEEE Transactions on Power Apparatus and Systems, 1983