380 kV corona ring optimization for AC voltages
Authors:
- 28 March 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 18 (2) , 408-417
Abstract
This paper presents corona ring optimization for 380 kV V-insulator string composed of glass insulator units. The influence of the corona ring design parameters are examined not only with regard to 3D simulations but also laboratory tests. The purpose of the simulations is to find reasonable corona ring design parameters such as corona ring diameter, corona tube diameter and installation height on the point of effective field regulation around the critical region of the string. Indoor laboratory tests including radio interference voltage levels, corona inception voltages and ac flashover voltages are conducted on the centre phase of a full scaled tower both for experimental based corona ring design as well as verifications of the simulations. After both simulations and experimental based investigations, appropriate corona ring design parameters for the string are determined for effective field regulation, minimum interference level, ac flashover performance and economic point of view.Keywords
This publication has 7 references indexed in Scilit:
- Flashover performance of 380 kV V-strings with composite insulators under lightning and switching impulses2009
- Optimization of corona ring design for long-rod insulators using FEM based computational analysis2005
- Calculation of electric field and potential distribution along nonceramic insulators considering the effects of conductors and transmission towersIEEE Transactions on Power Delivery, 2000
- Comparison of several methods for calculating power line electromagnetic interference levels and calibration with long term dataIEEE Transactions on Power Delivery, 1992
- Sag and tension calculations for mountainous terrainIEE Proceedings C Generation, Transmission and Distribution, 1982
- Power Arc on Insulator Strings: Testing Procedures and Design of Guard Devices for HV Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1970
- Radio interference from high-voltage insulators and factors which affect the interference levelProceedings of the Institution of Electrical Engineers, 1965