Parallel Operation of Bidirectional Interfacing Converters in a Hybrid AC/DC Microgrid Under Unbalanced Grid Voltage Conditions
Authors:
- 20 April 2016
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 32 (3) , 1872-1884
Abstract
Today, interests on hybrid ac/dc microgrids, which contain the advantages of both ac and dc microgrids, are growing rapidly. In the hybrid ac/dc microgrid, the parallel-operated ac/dc bidirectional interfacing converters (IFCs) are increasingly used for large capacity renewable energy sources or as the interlinking converters between the ac and dc subsystems. When unbalanced grid faults occur, the active power transferred by the parallel-operated IFCs must be kept constant and oscillation-free to stabilize the dc bus voltage. However, under conventional control strategies in unbalanced grid conditions, the active power transfer capability of IFCs is affected due to the converters' current rating limitations. Moreover, unbalanced voltage adverse effects on IFCs (such as output power oscillations, dc-link ripples, and output current enhancement) could be amplified by the number of parallel converters. Therefore, this paper investigates parallel operation of IFCs in hybrid ac/dc microgrids under unbalanced ac grid conditions and proposes a novel control strategy to enhance the active power transfer capability with zero active power oscillation. The proposed control strategy employs a new current sharing method which introduces adjustable current reference coefficients for parallel IFCs. In the proposed control strategy, only one IFC, named as redundant IFC, needs to be designed and installed with higher current rating to ensure the constant and oscillation-free output active power of parallel IFCs. Simulation and experimental results verify the feasibility and effectiveness of the proposed control strategy.Keywords
Funding Information
- National High Technology Research and Development Program (2015AA050606)
- National International Science and Technology Cooperation (2014DFG62610)
- National Natural Science Foundation of China (51177083)
- State Key Lab of Power Systems (SKLD14M01)
- Tsinghua University, China
This publication has 33 references indexed in Scilit:
- DG control strategies for grid voltage unbalance compensation2014
- Asymmetrical fault ride-through of three-phase PV systems using four-wire Dc-ac converters2014
- Power Control and Management in a Hybrid AC/DC MicrogridIEEE Transactions on Smart Grid, 2014
- Distributed control of hybrid AC-DC microgrid with solar energy, energy storage and critical load2014
- Design and analysis of active power control strategies for distributed generation inverters under unbalanced grid faultsIET Generation, Transmission & Distribution, 2010
- New positive-sequence voltage detector for grid synchronization of power converters under faulty grid conditions2006
- A Method for Synchronization of Power Electronic Converters in Polluted and Variable-Frequency EnvironmentsIEEE Transactions on Power Systems, 2004
- Design and implementation of a current controller for the parallel operation of standard UPSs2002
- Transient operation of grid-connected voltage source converter under unbalanced voltage conditions2002
- Dual current control scheme for PWM converter under unbalanced input voltage conditionsIEEE Transactions on Industrial Electronics, 1999