Long front time switching impulse tests of long air gap in UHV projects at altitude of 2100 m
Authors:
- 16 June 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 21 (3) , 982-987
Abstract
The past and recent investigations show that front time of switching overvoltage waveforms in Ultra High Voltage (UHV) system of long distance transmission are mostly in long wave front time exceeding 1000 μs. The long front time of switching impulse voltage has been deviated from the critical front time. This paper is involved with breakdown characteristics and external insulation design under long front switching impulse voltage in UHV system. All the Tests were performed on an outdoor UHV test site at altitude of 2100 m, China Southern Power Grid Co. Ltd. (CSG). Breakdown characteristics of rod-plane and actual size tower-conductor in ±800 kV UHV DC transmission line are obtained under wide front time switching impulse voltages from 100 to 2350 μs. From the comprehensive studies of such tests, it is proposed that U 50 of front time exceeding 1000 μs increases 20% compared with the results of standard switching impulse (250/2500 μs) tests and standard deviations of U 50 is 6% in UHV transmission system. Finally, an air gap insulation design procedure in conductor-tower of UHV transmission line at altitude of 0-2000 m is presented. Long front time switching impulse strength of conductor-tower gap is proposed into selection by reference in UHV transmission line insulation design.Keywords
This publication has 9 references indexed in Scilit:
- Study on switching impulse test waveform for UHV-class electric power equipmentIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Included Angle Selection of V-Shape Insulator String for 750-kV Compact Transmission LineIEEE Transactions on Power Delivery, 2010
- Comparison and analysis on over-voltage and insulation coordination of UHV AC transmission system between China and Japan2010
- Switching overvoltage analysis and air clearance design on the KEPCO 765 kV double circuit transmission systemIEEE Transactions on Power Delivery, 2000
- "Switching Impulse Strength Of Phase-To-Earth UHV External Insulation" - Research At The 1000KV Project -IEEE Transactions on Power Apparatus and Systems, 1985
- Switching Impulse Tests at Project UHV Using Longwave FrontsIEEE Transactions on Power Apparatus and Systems, 1981
- General expression for positive switching impulse strength valid up to extra long air gapsIEEE Transactions on Power Apparatus and Systems, 1975
- The Front Shape of Switching Impulses and its Effect on Breakdown ParametersIEEE Transactions on Power Apparatus and Systems, 1974
- Switching Surges with Very Long Fronts (above 1500 μs): Effect of Front Shape on Discharge VoltageIEEE Transactions on Power Apparatus and Systems, 1970