Anti-Islanding Protection Relay for Medium Voltage Feeder With Multiple Distributed Generators
Authors:
- 17 April 2017
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 64 (10) , 7874-7885
Abstract
Large distributed generators (DGs) are usually connected to medium voltage (MV, typically up to 50 kV) feeders directly. Their anti-islanding protections mainly rely on transfer trips from upstream substations through communication media, which are expensive and time-consuming because of infrastructure. This paper presents a local anti-islanding protection relay (LPR) as an alternative for the traditional transfer trip in MV feeder applications. The basic idea of the proposed LPR is to short phase to neutral or phase to phase voltages by thyristors at the point of common coupling (PCC) of each DG when either of them is crossing zero; then both variations of the thyristor current and voltage harmonic distortion at the PCC are observed and measured, and they are able to indicate the operating mode of the DG unit in either grid-connected or islanding. Further, this approach is analyzed and discussed based on a single DG scenario and a complicated scenario with two DGs and one shunt capacitor bank. Finally, a lot of experiment results with different scenarios are obtained based on a scale-down testing platform, which has been built in our lab by using per-unit method from an actual MV feeder system.Keywords
Funding Information
- Hydro One Foundation (HO1303)
- Project of State Grid Science and Technology (SGTYHT/14-JS-188)
This publication has 26 references indexed in Scilit:
- An Islanding Detection Method for Multi-DG Systems Based on High-Frequency Impedance EstimationIEEE Transactions on Sustainable Energy, 2016
- A testing platform for distribution grid with multiple grid-connected converters2016
- On the Experimental Performance of a Coordinated Antiislanding Protection for Systems With Multiple DGUsIEEE Transactions on Power Electronics, 2016
- Wide-Area Phase-Angle Measurements for Islanding Detection—An Adaptive Nonlinear ApproachIEEE Transactions on Power Delivery, 2016
- New Low-Distortion $Q$–$f$ Droop Plus Correlation Anti-Islanding Detection Method for Power Converters in Distributed Generation SystemsIEEE Transactions on Industrial Electronics, 2015
- Principal Component Analysis of Wide-Area Phasor Measurements for Islanding Detection—A Geometric ViewIEEE Transactions on Power Delivery, 2015
- Reviewing of anti-islanding protection2014
- Overview of anti-islanding US patents for grid-connected invertersRenewable and Sustainable Energy Reviews, 2014
- Smart grid and renewable energy systems2011
- New results for power line carrier-based islanding detection and an updated strengths and weaknesses discussion2011