Abstract
Real-time multiple event analysis is important for reliable situational awareness (SA) and secure operation of power system. Multiple sequential events can induce complex superimposed pattern in the data and are challenging to analyze in real-time. This paper proposes a method for accurate detection, temporal localization, and classification of multiple events in real-time using synchrophasor data. For detection and temporal localization, a Teager-Kaiser energy operator (TKEO) based method is proposed. For event classification, a time series classification based method using energy similarity measure (ESM) is proposed. The proposed method is tested for simulated multiple event cases in IEEE-118 bus system using DigSilent/PowerFactory and real PMU data for India grid.
Funding Information
  • Ministry of Human Resource and Development, New Delhi (IIT/SRIC/R/SEG/2014/295)

This publication has 25 references indexed in Scilit: