The Measurement Method for Corona Discharge Current Under High-Voltage Environment
Authors:
- 16 July 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 57 (8) , 1786-1790
Abstract
Measuring corona discharge current directly on the high-voltage side is essential for the discharge mechanism research of the test object. The amplitude of the corona discharge current is in microamperes, and its frequency ranges from DC to megahertz. An optical microcurrent transducer for measurement of the current is described in this paper based on an amplitude modulation principle. A low-pass filter is used to extend the analog fiber link to recover low-frequency signals. The uncertainty of the transducer is estimated to be less than 1.3% in ratio, and its response frequency range is from DC to several megahertz.Keywords
This publication has 9 references indexed in Scilit:
- Optical Micro-current Transducer for the Measurement of Corona Discharge Current Under High Voltage Environment2007
- An Optically Isolated Hybrid Two-Stage Current Transformer for Measurements at High VoltageIEEE Transactions on Instrumentation and Measurement, 2006
- Practical Application of Fiber-Optic Current Sensor in Power System Harmonic MeasurementIEEE Transactions on Instrumentation and Measurement, 2006
- A new hybrid current sensor for high-voltage applicationsIEEE Transactions on Power Delivery, 2005
- Development of a Portable Fiber-Optic Current Sensor for Power Systems MonitoringIEEE Transactions on Instrumentation and Measurement, 2004
- Optical decoupling in measurements of corona currents2003
- An analog fiber optic link for ESD detection2003
- Data acquisition system for the measurements of corona currents2002
- DC corona discharge of a metal filament particle within parallel-plate electrodesIEEE Transactions on Industry Applications, 2000