Monitoring Long Term Voltage Instability Due to Distribution and Transmission Interaction Using Unbalanced $\mu$ PMU and PMU Measurements
- 21 May 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 11 (1) , 873-883
Abstract
This paper extends the idea of the Thevenin equivalent into unbalanced $3\phi $ circuits and proposes a $3\phi $ long-term voltage stability indicator (VSI), that can identify critical loads in a $3\phi $ system. Furthermore, in order to identify whether the voltage stability limit is due to the transmission network or a distribution network, a transmission-distribution distinguishing index (TDDI) is proposed. The novelty in the proposed indices is that they can account for the unbalance in the lines and loads, enabling them to use unbalanced phasor measurements naturally. This is supported by mathematical derivations and numerical results. A convex optimization formulation to estimate the $3\phi $ Thevenin equivalent using PMU and $\mu $ PMU measurements is proposed, making it possible to calculate VSI and TDDI in an online model-free manner. Numerical simulations performed using co-simulation between Pypower and GridlabD are presented for the IEEE 9 bus and the 30 bus transmission networks combined with several modified IEEE 13 node and 37 node distribution networks. These case studies validate the proposed $3\phi $ -VSI and TDDI over a wide range of scenarios and demonstrate the importance of $\mu $ PMU measurements in identifying the regions causing long term voltage instability.
Keywords
All Related Versions
Funding Information
- National Science Foundation
- U.S. Department of Energy
This publication has 13 references indexed in Scilit:
- A Distributed Transmission-Distribution-Coupled Static Voltage Stability Assessment Method Considering Distributed GenerationIEEE Transactions on Power Systems, 2017
- Long-term voltage stability assessment of an integrated transmission distribution system2017
- Precision Micro-Synchrophasors for Distribution Systems: A Summary of ApplicationsIEEE Transactions on Smart Grid, 2017
- Sensitivity Based Thevenin Index With Systematic Inclusion of Reactive Power LimitsIEEE Transactions on Power Systems, 2017
- Decoupled voltage stability assessment of distribution networks using synchrophasors2016
- Existence and Uniqueness of Load-Flow Solutions in Three-Phase Distribution NetworksIEEE Transactions on Power Systems, 2016
- Master–Slave-Splitting Based Distributed Global Power Flow Method for Integrated Transmission and Distribution AnalysisIEEE Transactions on Smart Grid, 2014
- A short survey of methods for voltage instability detection2011
- Convex Optimization2004