Abstract
The introduction of phasor measurement unit (PMU) technology is generally expected to significantly improve existing state estimation (SE) algorithms regarding accuracy, observability, convergence. Since PMUs measure current and voltage phasors, in case of complete observability of all the network with PMUs, the PMU based SE will be linear, and consequently the SE algorithm faster and more accurate. Indeed, the complete observability of the network just with PMUs is, for many transmission system operators (TSOs), quite far to be reached; therefore, it becomes necessary to find suitable strategies in order to use all data by PMUs, in the best way in the classical SE. This paper deals with the possibility of using PMUs information in the classical real time least squares SE, with particular attention to the Italian case. Simulations on the complete 380/220 kV Italian transmission system are reported, in order to show the obtained benefits.Keywords
This publication has 5 references indexed in Scilit:
- Observability and estimation of transformer tap setting with minimal PMU placement2008
- Synchronized phasor measurements-a historical overview2003
- A security oriented approach to PMU positioning for advanced monitoring of a transmission grid2003
- Phasor measurement unit placement based on incomplete observability2003
- PMU configuration for system dynamic performance measurement in large, multiarea power systemsIEEE Transactions on Power Systems, 2002