Analysis of air-to-water heat pump in cold climate: comparison between experiment and simulation
Open Access
- 29 September 2015
- journal article
- Published by Vilnius Gediminas Technical University in Mokslas - Lietuvos ateitis
- Vol. 7 (4) , 468-474
Abstract
Heat pump systems are promising technologies for current and future buildings and this research presents the performance of air source heat pump (ASHP) system. The system was monitored, analysed and simulated using TRNSYS software. The experimental data were used to calibrate the simulation model of ASHP. The specific climate conditions are evaluated in the model. It was noticed for the heating mode that the coefficient of performance (COP) varied from 1.98 to 3.05 as the outdoor temperature changed from –7.0 ºC to +5.0 ºC, respectively. TRNSYS simulations were also performed to predict seasonal performance factor of the ASHP for Vilnius city. It was identified that seasonal performance prediction could be approximately 15% lower if frost formation effects are not included to air-water heat pump simulation model.Keywords
This publication has 9 references indexed in Scilit:
- Comparative thermal performances of a ground source heat pump and a variable capacity air source heat pump systems for sustainable housesApplied Thermal Engineering, 2015
- Influence of Outdoor Air Conditions on the Air Source Heat Pumps PerformanceEnergy Procedia, 2014
- A novel defrosting control method based on the degree of refrigerant superheat for air source heat pumpsInternational Journal of Refrigeration, 2013
- Study on the operating performance of cross hot-gas bypass defrosting system for air-to-water screw heat pumpsApplied Thermal Engineering, 2013
- A new method for preventing air-source heat pump water heaters from frostingInternational Journal of Refrigeration, 2012
- An experimental study on defrosting heat supplies and energy consumptions during a reverse cycle defrost operation for an air source heat pumpApplied Thermal Engineering, 2012
- A study of the reverse cycle defrosting performance on a multi-circuit outdoor coil unit in an air source heat pump – Part II: Modeling analysisApplied Energy, 2012
- Uncertainties in heat-pump coefficient of performance (COP) and exergy efficiency based on standardized testingEnergy and Buildings, 2011
- Ground-source heat pumps systems and applicationsRenewable and Sustainable Energy Reviews, 2008