Research on Reactive Power Optimization of Synchronous Condensers in HVDC Transmission Based on Reactive Power Conversion Factor
Open Access
Abstract
With the rapid development of high-voltage direct current (HVDC) transmission systems, the coupling between AC and DC grids is becoming increasingly close. Voltage disturbances in the grid can easily cause commutation failures in the DC system, threatening its safe and stable operation. The new generation of synchronous condensers (SCs) and modified synchronous condenser units are powerful reactive power support devices widely used in large-capacity DC transmission systems. To maximize the voltage support and commutation failure suppression of SCs, this paper proposes improvements in the initial operating state of SCs, using the Shanxi–Wuhan HVDC receiving end in the Hubei power grid as an example, to better support the HVDC commutation process. Additionally, a reactive power output optimization strategy for SCs is proposed, considering the reactive power equivalent factor of electrical connections between grid nodes. This strategy determines the optimal reactive power output limit of SCs near the converter station to suppress DC commutation failures. Simulation results show that this strategy effectively utilizes the dynamic support capabilities of SCs, prevents DC commutation failures, improves HVDC transmission capacity, and enhances the safety and stability of the receiving end power grid, providing theoretical guidance for reactive power output control.Keywords
Funding Information
- National Natural Science Foundation of China (51677012)
This publication has 26 references indexed in Scilit:
- Identifying optimal combinations of synchronous condensers for minimum grid strength complianceInternational Journal of Electrical Power & Energy Systems, 2024
- Analysis of transient electromagnetic force on end windings of 300 Mvar synchronous condenser during dynamic reactive power compensation processInternational Journal of Electrical Power & Energy Systems, 2023
- Fault indicator based on stator current under early stage SISC in synchronous condensersEngineering Failure Analysis, 2022
- Multi-Criteria based Steady-State and Dynamic Reactive Power Planning for Transmission SystemsElectric Power Systems Research, 2022
- Parameter setting method of coordinated control between synchronous condenser and DC system based on dynamic reactive power optimizationIET Generation, Transmission & Distribution, 2022
- Transient stability emergency control for AC/DC grids considering successive commutation failuresIET Generation, Transmission & Distribution, 2021
- Reactive power characteristics and vibration properties under SISC in synchronous condensersInternational Journal of Electrical Power & Energy Systems, 2021
- Automatic Voltage Control of Large-scale Synchronous Condensers in UHV-DC Converter Station2021
- Dynamic reactive power optimisation of UHVDC converter station considering coordination of synchronous condenser and system filtering requirementsIET Generation, Transmission & Distribution, 2020
- Simulation and analysis of cascading faults in hybrid AC/DC power gridsInternational Journal of Electrical Power & Energy Systems, 2020