Algorithm for Designing the Size of Energy Storage in Dynamic Voltage Restorer
Author:
- 1 August 2006
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 21647011,p. 46-51
Abstract
A large capacity of the energy storage unit in a dynamic voltage restorer (DVR) may result in a significant cost of using DVR that may not be justified in the case where the number of severe voltage sags is extremely low over the lifespan of DVR. However, a significant reduction in the capacity of the energy storage unit may not guarantee that the voltage supply filtered by DVR is compatible with the sensitivity of the protected load. To achieve a balance between the compatibility and the cost saving of using DVR, an algorithm is developed and integrated with a voltage sag prediction method to derive two essential bar charts. By using these bar charts and the available voltage tolerance curve of the protected load, one can determine the optimum capacity of the energy storage unit that may ensure a balance between the compatibility and the maximum cost saving of using DVRKeywords
This publication has 5 references indexed in Scilit:
- Voltage sag compensation with energy optimized dynamic voltage restorerIEEE Transactions on Power Delivery, 2003
- Control strategies for dynamic voltage restorer compensating voltage sags with phase jump2002
- Analytical approach to probabilistic prediction of voltage sags on transmission networksIEE Proceedings - Generation, Transmission and Distribution, 2002
- DRPT 2000 ReviewIEEE Power Engineering Review, 2001
- Dynamic voltage restoration with minimum energy injectionIEEE Transactions on Power Systems, 2000