Online Condition Assessment of Interruption Chamber of Gas Circuit Breakers Using Arc Voltage Measurement
- 2 August 2016
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 32 (4) , 1776-1783
Abstract
As a key element of a power system, a circuit breaker (CB) requires regular maintenance. Intelligent online condition assessment is increasingly becoming a requirement for key items of power plants, including CBs. The interruption chamber, as the most critical part of the CBs, plays an important role in the proper operation of CBs. Online assessment of this part is difficult from a technical perspective due to the high noise level and presence of a transient recovery voltage. This paper proposes a set up for the online measurement of the CB arc voltage during trip/close operations. In addition, a method has been proposed to evaluate the remaining useful lifetime of the interruption chamber based on the measured arc voltage and current. The setup and the proposed approach are verified experimentally.Keywords
This publication has 21 references indexed in Scilit:
- Circuit breaker condition assessment through a fuzzy‐probabilistic analysis of actuating coil's currentIET Generation, Transmission & Distribution, 2016
- Applicability of auxiliary contacts in circuit breaker online condition assessmentElectric Power Systems Research, 2015
- Optimal Test Current Shape for Accurate Arc Characteristic DeterminationIEEE Transactions on Power Delivery, 2014
- Circuit-Breaker Automated Failure Tracking Based on Coil Current SignatureIEEE Transactions on Power Delivery, 2013
- Priority Assessment of Online Monitoring Investment for Power System Circuit Breakers—Part I: Qualitative-Quantitative ApproachIEEE Transactions on Power Delivery, 2013
- A Novel Smart High-Voltage Circuit Breaker for Smart Grid ApplicationsIEEE Transactions on Smart Grid, 2011
- Life management of SF6 circuit breakers based on monitoring and diagnosisIEEE Electrical Insulation Magazine, 2009
- Investigation on Erosion of Cu/W Contacts in High-Voltage Circuit BreakersIEEE Transactions on Components and Packaging Technologies, 2006
- An Improved Arc Model Before Current Zero Based on the Combined Mayr and Cassie Arc ModelsIEEE Transactions on Power Delivery, 2005
- Development and improvement of digitized measuring system of arc voltage for high voltage circuit breaker2003