Development and validation of simple-shield thermocouple in fire environments
Authors:
- 20 October 2020
- journal article
- research article
- Published by SAGE Publications in Journal of Fire Sciences
- Vol. 39 (1) , 53-71
Abstract
A novel simple-shield thermocouple that is capable of radiation correction in fire environments and that has a simpler structure and greater convenience than conventional aspirated thermocouples was proposed. The measurement errors of bare-bead, double-shield aspirated, and simple-shield thermocouples were then compared in a simulated fire environment. In addition, a fire experiment using wood cribs was performed in order to verify the measurement performance of the proposed simple-shield thermocouple in a real fire environment using a one-third-scale ISO 9705 room. The simple-shield thermocouple produced fairly accurate temperatures that fell within 5% of the actual gas temperature in the simulated fire environment. In addition, variations in the surface emissivity and the installation angle of the simple-shield thermocouple in the real fire environment further reduced the measurement error. With a radiant heat flux of 20 kW/m2, it was confirmed that the bare-bead thermocouple had a relative measurement error of up to 80% compared to the aspirated thermocouple, while the proposed simple-shield thermocouple was capable of measuring the temperature within a relative error of around 15% compared to the aspirated thermocouple.Keywords
Funding Information
- the National Fire Agency (2015-NFA001-004)
This publication has 18 references indexed in Scilit:
- Assessment of radiation correction methods for bare bead thermocouples in a combustion environmentInternational Journal of Thermal Sciences, 2017
- On the Temperature Measurement Bias and Time Response of an Aspirated Thermocouple in Fire EnvironmentJournal of Fire Sciences, 2008
- A two-thermocouples probe for radiation corrections of measured temperatures in compartment firesFire Safety Journal, 2004
- Modeling of bare and aspirated thermocouples in compartment firesFire Safety Journal, 1999
- Effects of Radiation on Temperature Measurement in a Fire EnvironmentJournal of Fire Sciences, 1997
- On the Use of Metal Sheathed Thermocouples in a Hot Gas Layer Originating from a Room FireJournal of Fire Sciences, 1995
- Thermocouples and sample probes for combustion studiesProgress in Energy and Combustion Science, 1993
- The Calibration of thermocouples and thermocouple materials1989
- Fine Wire Thermocouple Measurements of Fluctuating TemperatureCombustion Science and Technology, 1977