The influence of square voltage waveforms on transformer insulation break down voltage
Authors:
- 1 October 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 48-51
Abstract
The use of Voltage Source Converters (VSCs) in HVDC transmission and, more generally, in flexible AC transmission systems (FACTS), raises concerns over the endurance of turn/turn insulation of grid/converter interface transformers. In this paper, tests performed on oil-impregnated paper specimens are discussed. The results indicate clearly that shorter rise times and higher repetition frequencies have a strong impact on both partial discharge inception voltage and breakdown voltage. These results suggest that deeper investigation might be important to understand the long term behavior of these insulation systems.Keywords
This publication has 9 references indexed in Scilit:
- The effects of prolonged exposure of paper insulation to fast repeating transients2010
- Investigation of the effects of fast transients on a transformer's paper insulation2010
- SiC power devices for Smart Grid systems2010
- A UHF Technique for Advanced PD Measurements on Inverter-Fed MotorsIEEE Transactions on Power Electronics, 2008
- AC Grid with Embedded VSC-HVDC for Secure and Efficient Power Delivery2008
- Practical medium voltage converter topologies for high power applications2002
- Application of HVDC Light to power system enhancement2002
- The effect of voltage distortion on ageing acceleration of insulation systems under partial discharge activityIEEE Electrical Insulation Magazine, 2001
- Failure mechanism of the interturn insulation of low voltage electric machines fed by pulse-controlled invertersIEEE Electrical Insulation Magazine, 1996