Characteristics of Electromagnetic Disturbance for Intelligent Component Due to Switching Operations via a 1100 kV AC GIS Test Circuit
Authors:
- 15 August 2016
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 32 (5) , 2228-2237
Abstract
Switching operation of the disconnector in gas-insulated switchgear (GIS) results in very fast transient overvoltage in GIS pipes. In a smart substation, this process induces disturbance voltage on the port of the intelligent component fixed on GIS pipes or placed in the local cabinet nearby, which then may lead to the failure of the equipment. The experimental results of the port disturbance voltage during the switching operation via a 1100 kV test circuit are first reported in this paper. The test arrangement, including both 70 opening operations and 70 closing operations, had been performed. The influences of different grounding schemes of cable shield on port disturbance had been investigated. Three different cases of the terminal load had also been considered: open circuit, short circuit, and 50 Ω. Over 100 000 micro-pulses had been extracted from the disturbance voltage waveforms. The waveform characteristics including peak voltage, rise-time, oscillation frequency, and decaying had been obtained by statistical analysis of these micro-pulses. Furthermore, the differences between measured waveforms and the IEC 61000-4-18 immunity test standard waveform had been discussed.Keywords
Funding Information
- Science and Technology Project of SGCC (GYB17201400111)
This publication has 17 references indexed in Scilit:
- Improved Cable Connection to Mitigate Transient Enclosure Voltages in 220-kV Gas-Insulated SubstationsIEEE Transactions on Industry Applications, 2015
- A Circuit Model of Transverse Electric Eddy-Current Problems in Magnetic RingsIEEE Transactions on Magnetics, 2015
- Study on the Influence of Disconnector Characteristics on Very Fast Transient Overvoltages in 1100-kV Gas-Insulated SwitchgearIEEE Transactions on Power Delivery, 2015
- Experimental Research and Simulation on VFTO Mitigation by Ferrite Rings in UHV GISIEEE Transactions on Power Delivery, 2014
- New Methods of Damping Very Fast Transient Overvoltages in Gas-Insulated SwitchgearIEEE Transactions on Power Delivery, 2014
- Experimental Research on Very-Fast Transient Overvoltage in 1100-kV Gas-Insulated SwitchgearIEEE Transactions on Power Delivery, 2012
- Transient Enclosure Voltage (TEV) measurement system of UHV GIS and TEV statistical characterization2012
- Analysis of transient surge transmission characteristics of electronic circuits due to arc discharge generated with disconnector on/off in GISElectrical Engineering in Japan, 2004
- Transient electromagnetic phenomena in the secondary circuits of voltage and current transformers in GIS (measurements and calculations)IEEE Transactions on Power Delivery, 2001
- Induced transients in substation cables: measurements and modelsIEEE Transactions on Power Delivery, 1994