Theoretical analysis on the VSC instability caused by PLL in weak system
Authors:
Open Access
- 9 June 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 14 (10) , 1782-1788
Abstract
The mechanism of voltage sourced converter's (VSC) instability caused by phase‐locked‐loop (PLL) in weak system is revealed in a simplified and efficient way. Based on the key‐variables small signals model, the PLL's impact to VSC stability is described by the defined low frequency torque and high frequency torque. The low frequency torque decides the characteristic of VSC in low frequency domain, and supplies synchronous ability and low frequency damping to VSC, while the high frequency torque decides VSC's high frequency characteristic and supply high frequency damping. The two torques impact factors are researched and their influences are revealed. It is found that to keep system stable, sufficient torques are needed. Because weakening system strength will decrease both torques, the mechanism of the instability caused by PLL in weak system is actually lack of sufficient torques. The simulation based on PSCAD software is implemented to validate the theory and matches well with the proposed theory.Keywords
Funding Information
- National Key Research and Development Program of China
This publication has 20 references indexed in Scilit:
- Current Error Based Compensations for VSC Current Control in Weak Grids for Wind Farm ApplicationsIEEE Transactions on Sustainable Energy, 2018
- Robust Vector Control of a Very Weak-Grid-Connected Voltage-Source Converter Considering the Phase-Locked Loop DynamicsIEEE Transactions on Power Electronics, 2016
- DC-Bus Voltage Control Stability Affected by AC-Bus Voltage Control in VSCs Connected to Weak AC GridsIEEE Journal of Emerging and Selected Topics in Power Electronics, 2015
- Identification and Small-Signal Analysis of Interaction Modes in VSC MTDC SystemsIEEE Transactions on Power Delivery, 2015
- Operation, Control, and Applications of the Modular Multilevel Converter: A ReviewIEEE Transactions on Power Electronics, 2015
- Impact of Short-Circuit Ratio and Phase-Locked-Loop Parameters on the Small-Signal Behavior of a VSC-HVDC ConverterIEEE Transactions on Power Delivery, 2014
- VSC transmission limitations imposed by AC system strength and AC impedance characteristics2012
- Modeling and Control of VSC-HVDC Links Connected to Island SystemsIEEE Transactions on Power Systems, 2010
- Evaluation of current controller performance and stability for voltage source converters connected to a weak grid2010
- Interconnection of Two Very Weak AC Systems by VSC-HVDC Links Using Power-Synchronization ControlIEEE Transactions on Power Systems, 2010