Thermal analysis and derating of a power transformer with harmonic loads
Open Access
- 26 February 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 14 (7) , 1233-1241
Abstract
Thermal conditions of power transformers in abnormal operating conditions such as harmonic loads can be considered as a critical case. In this study, thermal analysis of transformer and additional imposed heat on it, caused by non‐linear loads, are addressed. For this purpose, an appropriate thermal equivalent circuit is used in which temperature of different parts of oil‐immersed power transformers are obtained for harmonic loads. The losses of various components of transformer as heat‐generating sources are estimated. At this end, an appropriate three‐dimensional finite element method is applied to estimate the losses of different parts of transformer. To keep the transformer temperature rise around the permissible value, the transformer is derated. Transformer derating based on the IEEE Std C57.110–2008 recommendation considerably reduces the transformer loading capability. Therefore, this study introduces a new technique for derating of transformer for harmonic loads. This enhances the transformer thermal limits and transformer loading capacity.Keywords
This publication has 27 references indexed in Scilit:
- Is Transformer kVA Derating Always Required Under Harmonics? A Manufacturer's PerspectiveIEEE Transactions on Power Delivery, 2018
- Derating of distribution transformers under non‐linear loads using a combined analytical‐finite elements approachIET Electric Power Applications, 2016
- Modeling and simulation of transformer loading capability and hot spot temperature under harmonic conditionsElectric Power Systems Research, 2012
- Mixed Derating of Distribution Transformers Under Unbalanced Supply Voltage and Nonlinear Load Conditions Using TSFEMIEEE Transactions on Power Delivery, 2010
- Dynamic Thermal Modeling of Power Transformers: Further Development—Part IIEEE Transactions on Power Delivery, 2006
- Derating of a distribution transformer for non-linear loadsEuropean Transactions on Electrical Power, 2005
- Dynamic Thermal Modelling of Power TransformersIEEE Transactions on Power Delivery, 2005
- A fundamental approach to transformer thermal modeling. I. Theory and equivalent circuitIEEE Transactions on Power Delivery, 2001
- A procedure for derating a substation transformer in the presence of widespread electric vehicle battery chargingIEEE Transactions on Power Delivery, 1997
- Temperature Rise of an Oil-Filled Transformer with Varying LoadIEEE Transactions on Power Apparatus and Systems, 1984