Numerical and Experimental Investigation on the Effect of Mechanical Smoke Extraction Caused by External Wind in Subway Station Halls
Open Access
- 24 November 2022
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 12 (23) , 12014
Abstract
When fires break out in subway station halls, traditional smoke extraction (TSE) systems are employed with the aim of preventing smoke from spreading to the platform and passageways. The functionality of TSE systems under the influence of external winds needs to be further explored. Based on a numerical method, this study investigated the effect on TSE systems under the influence of external wind. A numerical model was established and validated by means of full-scale field tests to ensure accuracy. Subsequently, the validated model was applied to study the effect of the external wind directions and speeds on the smoke diffusion distance. The results showed that when all entrances and exits were on the windward side, the external wind direction led to serious longitudinal diffusion of the smoke toward the side with fewer entrances and exits of the station hall, and the diffusion distance increased with increasing wind speed. The diffusion distance reached a maximum value of 61.32 m when the outdoor wind was 5 m/s, which was 67.9% higher than that under no wind. When all the entrances and exits were on the leeward side, the external wind had little influence on the degree of smoke spread, with the greatest smoke diffusion distance being only 4.76% longer than that under no wind. When two entrances and exits were on the windward side and the other on the leeward side, the external wind caused smoke to spread to a passageway, and the degree of smoke spread was more unfavorable at higher wind speeds, with the longest diffusion distance being 7.28 m. To prevent smoke from spreading to passageways and to effectively shorten the longitudinal diffusion distance of smoke, an optimized smoke control (OSC) system was proposed, employing center and passageway smoke barriers, which were able to shorten the diffusion distances by 35.45%, 13.64%, and 2.35%. In particular, smoke diffusion did not occur in passageways. This study provides a reference for the fire safety engineering design of subway stations.Keywords
Funding Information
- the National Key R&D Program of China (2021YFC2600500)
This publication has 27 references indexed in Scilit:
- Smoke spreading analysis from an experimental subway scale modelFire Safety Journal, 2016
- Full-scale fire experiments and simulation of tunnel with vertical shaftsApplied Thermal Engineering, 2016
- A STUDY OF THE FIRE SMOKE PROPAGATION IN SUBWAY STATION UNDER THE EFFECT OF PISTON WINDJOURNAL OF CIVIL ENGINEERING AND MANAGEMENT, 2015
- Fire-induced smoke control via hybrid ventilation in a huge transit terminal subway stationEnergy and Buildings, 2012
- Effectiveness of downward evacuation in a large-scale subway fire using Fire Dynamics SimulatorTunnelling and Underground Space Technology, 2011
- CFD simulation and assessment of life safety in a subway train fireTunnelling and Underground Space Technology, 2009
- AIJ guidelines for practical applications of CFD to pedestrian wind environment around buildingsJournal of Wind Engineering and Industrial Aerodynamics, 2008
- About Boussinesq's turbulent viscosity hypothesis: historical remarks and a direct evaluation of its validityComptes Rendus Mécanique, 2007
- Numerical predictions of smoke movement in a subway station under ventilationTunnelling and Underground Space Technology, 2006
- Safety evaluation of engineering and construction projects in ChinaJournal of Loss Prevention in the Process Industries, 2003