This paper presents the design and testing of a full scale 330-kV, 210-MVA transformer tank to withstand the pressure effects of a 20 MJ, three-cycle low impedance fault in oil, and fail at its cover in a safe and controlled manner above that amount of energy. The transformer tank, equipped with a mockup active part, was designed for arc resistance using nonlinear static finite-element analysis and a specific rupture criterion. It was then tested using an experimental methodology based on inject-ing pressurized air into the water-filled tank. To adequately reproduce the effects of an arc in oil, the test parameters were determined using explicit dynamic simulations. The transformer tank performed as predicted by the finite-element and explicit dynamic simulations. The energy levels used in the tests here are, to our knowledge, the largest ever reported. This study demonstrates that it is feasible to design a power transformer to safely withstand high-energy low-impedance faults of short duration.Keywords
This publication has 8 references indexed in Scilit:
- A Comparison of Numerical Methods for Modeling Overpressure Effects from Low Impedance Faults in Power TransformersProcedia Engineering, 2017
- Numerical Method for the Investigation of Fault Containment and Tank Rupture of Power TransformersIEEE Transactions on Power Delivery, 2010
- Pressure wave propagation induced by short circuits inside power transformers: Development of a simulation tool, comparisons with experiments and applicationsThe International Journal of Multiphysics, 2009
- Power Transformer Tank Rupture and Mitigation—A Summary of Current State of Practice and Knowledge by the Task Force of IEEE Power Transformer SubcommitteeIEEE Transactions on Power Delivery, 2009
- Estimating overpressures in pole-type distribution transformers. II. Prediction toolsIEEE Transactions on Power Delivery, 2003
- Estimating overpressures in pole-type distribution transformers. I. Tank withstand evaluationIEEE Transactions on Power Delivery, 2003
- Computational methods for the analysis of explosions in oil-insulated electrical equipmentIEEE Transactions on Power Systems, 1988
- Tank Pressures Resulting from Internal ExplosionsTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1959