Validation and in-field testing of a new on-site qPCR system for quantification of Legionella pneumophila according to ISO/TS 12869:2012 in HVAC cooling towers
Authors:
Open Access
- 1 March 2019
- journal article
- research article
- Published by IWA Publishing in Journal of Water and Health
- Vol. 17 (2) , 237-253
Abstract
Legionella pneumophila, found in engineered water systems such as HVAC cooling towers, poses a significant public health risk. Culture, though routinely used to quantify L. pneumophila, has several disadvantages including long turnaround time, low sensitivity, and inter-lab variability. In this study, we validated the performance of an on-site qPCR detection system for L. pneumophila in accordance with International Standards Organization Technical Specification 12869:2012. We evaluated specificity, limit of detection and quantification, and calibration curve linearity. Additionally, we evaluated whole system recovery and robustness using samples taken from taps and evaporative cooling towers. We then compared the system's performance against laboratory culture and laboratory qPCR across 53 cooling towers in a 12-week in-field study. We found that concordance between on-site qPCR and culture was both laboratory- and site/sample-dependent. Comparison of laboratory qPCR with on-site qPCR revealed that laboratory results were highly variable and showed little concordance. Some discordance may be explained by time delay between sample collection and testing (‘shipping effect’) which may lead to inaccurate reporting. Overall, our study highlights the value of on-site qPCR detection of L. pneumophila, demonstrates that laboratories are prone to misreporting results due to shipping effects, and reveals significant discordance between laboratory qPCR and culture.Keywords
This publication has 27 references indexed in Scilit:
- Characterization and resuscitation of ‘non-culturable’ cells of Legionella pneumophilaBMC Microbiology, 2014
- Biofilms: The Stronghold of Legionella pneumophilaInternational Journal of Molecular Sciences, 2013
- Stationary phase and mature infectious forms of
L
egionella pneumophila
produce distinct viable but non‐culturable cellsEnvironmental Microbiology, 2013
- Accuracy and precision of Legionella isolation by US laboratories in the ELITE program pilot studyWater Research, 2011
- An international trial of quantitative PCR for monitoringLegionellain artificial water systemsJournal of Applied Microbiology, 2011
- Viability PCR, a Culture-Independent Method for Rapid and Selective Quantification of Viable Legionella pneumophila Cells in Environmental Water SamplesApplied and Environmental Microbiology, 2009
- Quantitative Real-Time Legionella PCR for Environmental Water Samples: Data InterpretationApplied and Environmental Microbiology, 2006
- Literature review—efficacy of various disinfectants against Legionella in water systemsWater Research, 2002
- Non‐culturable Legionella pneumophila associated with Acanthamoeba castellanii: detection of the bacterium using DNA amplification and hybridizationJournal of Applied Bacteriology, 1995
- Viable Legionella pneumophila Not Detectable by Culture on Agar MediaNature Biotechnology, 1987