On the Impact of High Penetration of Rooftop Solar Photovoltaics on the Aging of Distribution Transformers
- 1 August 2017
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Canadian Journal of Electrical and Computer Engineering
- Vol. 40 (2) , 93-100
Abstract
This paper investigates the effect of increasing the penetration of Rooftop Solar Photovoltaics (PVs) on a Distribution Transformer's (DT's) Loss of Life (LOL). The modeling of the secondary distribution system is introduced and the Markov chain Monte Carlo is used to probabilistically estimate the hourly loading on a DT while the LOL is estimated based on the DT's thermal model. The results have shown that the minimum impact on the DT's LOL may be only achieved at 60% penetration of PVs that can be considered as the maximum permissible solar PVs penetration level.Keywords
This publication has 20 references indexed in Scilit:
- Impact of Second-Generation Plug-In Battery Electric Vehicles on the Aging of Distribution Transformers Considering TOU PricesIEEE Transactions on Sustainable Energy, 2015
- The effect of PV on transformer ageing: University of Queensland's experience2014
- Power Quality Assessment in Distribution Systems Embedded With Plug-In Hybrid and Battery Electric VehiclesIEEE Transactions on Power Systems, 2014
- Impact of high PV penetration on distribution transformer life time2013
- Transformer and home energy management systems to lessen electrical vehicle impact on the gridIET Generation, Transmission & Distribution, 2012
- Effect of power system harmonics on transformer loading capability and hot spot temperature2012
- A Short History of Markov Chain Monte Carlo: Subjective Recollections from Incomplete DataStatistical Science, 2011
- A program for harmonic modeling of distribution network transformers and determination of loss in the transformers and the amount of decrease of their life2006
- Dynamic Thermal Modelling of Power TransformersIEEE Transactions on Power Delivery, 2005
- Distribution transformer loss of life evaluation: a novel approach based on daily load profilesIEEE Transactions on Power Delivery, 2000