The performance of atria in two school buildings
Author:
- D. J. HarrisDHD. J. Harris
- 1 October 1997
- journal article
- research article
- Published by Taylor & Francis in International Journal of Ambient Energy
- Vol. 18 (4) , 171-176
Abstract
Atria have become popular additions to many building types in recent years. There is a common misconception that they will automatically result in lower energy consumption, but this is not necessarily the case. Only when designed and used in an appropriate way will atria contribute to energy conservation. In this paper the performance of two school buildings, one incorporating a heated atrium, the other an unheated atrium, was studied. Comparisons between their performance were made with respect to thermal comfort, heating costs, overheating and daylighting. While heating the atrium incurred a cost penalty, it resulted in comfortable conditions in the space for a greater proportion of the time in winter, and consequently created a more useful space. In summer months overheating was likely unless an area of opening vents the equivalent of 10% or more of the floor area is provided in the atrium roof.Keywords
This publication has 1 reference indexed in Scilit:
- ‘Passive-solar’ schools in the UKApplied Energy, 1991