Analysis of Extruded HVDC Cable Systems Exposed to Lightning Strokes
Open Access
- 26 July 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 33 (6) , 3009-3018
Abstract
In high voltage direct current (HVDC) transmission systems comprising overhead-line (OHL) sections as well as cable sections, the dc cable system is exposed indirectly to lightning strokes. In case of HVDC cable systems with extruded insulation the present test recommendations do not specify lightning impulse test levels related to rated system voltage. Instead, preliminary electromagentic transient (EMT) studies are required to determine the absolute maximum lightning impulse voltage the cable might experience. Within this paper, the general lightning behaviour of OHL-cable mixed systems subsequent to the occurrence of a backflashover (BFO) as well as a shielding failure is investigated for a 525-kV HVDC transmission scheme. This paper presents a modelling method to calculate occurring lightning overvoltages along a dc cable embedded between OHL sections. Based on a detailed parametric study using time-domain simulation, maximum lightning impulse voltages along the cable system are determined and evaluated with regard to impulse level and polarity. The impact of project related parameter such as cable length, tower design and tower grounding conditions on lightning overvoltage affecting the cable is demonstrated.Keywords
This publication has 18 references indexed in Scilit:
- Maximum Lightning Overvoltage Along a Cable Protected by Surge ArrestersIEEE Transactions on Power Delivery, 2005
- A Method of a Lightning Surge Analysis Recommended in Japan Using EMTPIEEE Transactions on Power Delivery, 2005
- On High-Frequency Circuit Equivalents of a Vertical Ground RodIEEE Transactions on Power Delivery, 2005
- A universal model for accurate calculation of electromagnetic transients on overhead lines and underground cablesIEEE Transactions on Power Delivery, 1999
- Insulation Strength Characteristics1999
- Electric fields in HVDC paper-insulated cablesIEEE Transactions on Dielectrics and Electrical Insulation, 1998
- Experimental study and analysis of breakdown characteristics of long air gaps with short tail lightning impulseIEEE Transactions on Power Delivery, 1996
- Modeling guidelines for fast front transientsIEEE Transactions on Power Delivery, 1996
- Modelling of a transmission tower for lightning-surge analysisIEE Proceedings - Generation, Transmission and Distribution, 1996
- Modeling of metal oxide surge arrestersIEEE Transactions on Power Delivery, 1992