Improving the Efficiency of Earth Fault Detection by Fault Current Passage Indicators in Medium-Voltage Compensated Overhead Networks
Open Access
Abstract
The article presents a method for detecting earth faults in a compensated medium-voltage network, which can be used especially in fault current passage indicators, but also in standard protection devices. The method is based on the adaptation process of the zero-sequence current protection setting, with the adaptation factor depending on the current value of the zero-sequence voltage. In this article, a comparative analysis of the classical and adaptive zero-sequence current criterion is conducted, taking into account the errors of the measuring system. The results of simulations performed in the PSCad environment are also presented. For a representative set of example short circuits, it was shown that the effectiveness of the presented criterion can be more than 50% higher than that of the standard criteria, taking into account the range of detected transition resistances. A comparison of the proposed method with admittance criteria was also drawn, and it was shown that it is suitable for the detection of high-resistance earth faults.Keywords
Funding Information
- Ministry of Science and Higher Education (0711/SBAD/4560)
This publication has 40 references indexed in Scilit:
- Incipient Fault Location Algorithm for Underground CablesIEEE Transactions on Smart Grid, 2014
- A new approach to fault location in three-phase underground distribution system using combination of wavelet analysis with ANN and FLSInternational Journal of Electrical Power & Energy Systems, 2014
- A new fault location algorithm for radial distribution systems using modal analysisInternational Journal of Electrical Power & Energy Systems, 2013
- Single Phase Earth Fault Location in the Medium Voltage Distribution NetworksScientific Journal of Riga Technical University. Power and Electrical Engineering, 2009
- Comparison of impedance based fault location methods for power distribution systemsElectric Power Systems Research, 2008
- Application of wavelet fuzzy neural network in locating single line to ground fault (SLG) in distribution linesInternational Journal of Electrical Power & Energy Systems, 2007
- Numerical algorithm for overhead lines arcing faults detection and distance and directional protectionIEEE Transactions on Power Delivery, 2000
- Zero sequence directional earth-fault protection with improved characteristics for compensated distribution networksElectric Power Systems Research, 1999
- Characteristics of earth faults in electrical distribution networks with high impedance earthingElectric Power Systems Research, 1998
- Digital signal processing algorithm for arcing faults detection and fault distance calculation on transmission linesInternational Journal of Electrical Power & Energy Systems, 1997